CPX8216 and CPX8216T Installation and Use (6806800A52C)
93
9 Subassembly Removal and Installation
Overview
This chapter provides the removal and installation procedures for field-replaceable
subassemblies. Note that the CPX8216 backplane is not a field-replaceable unit.
These procedures should be performed by trained service personnel only. The list below shows
the subassembly removal/installation procedures included in this chapter.
Fan and Power Supply Sled Removal and Installation
Alarm Panel Removal and Installation (Hot Swap)
AC or DC Power Distribution Panel
Floppy Housing Removal and Installation
Fan and Power Supply Sled Removal and Installation
The CPX8216 chassis supports N+1 redundant power supplies. If the chassis is equipped with
a redundant power supply, the removal of a single power supply does not interrupt system
operation.
The following instructions describe how to remove and install a fan/power supply sled. The
instructions apply to both the AC and the DC versions of the power supply. There are also
procedures for the replacement of the fan module which is housed in the fan/power supply sled.